Storage systems invert the cable problem that PV presents. On a PV string, voltage is high and current is modest, so voltage drop dominates. Between a battery bank and an inverter, voltage is low and current is enormous — 100 A continuous is ordinary on a 48 V household system — so thermal capacity, heat dissipation and terminal quality dominate, and the voltage-drop budget collapses to a fraction of a volt. Cable chosen by PV instinct is almost always too small for a battery run.

This guide covers what changes, the arithmetic that decides it, and the protection details specific to lithium-based systems.

Why storage DC is a different problem from PV

Aspect PV string Battery to inverter
Typical voltage 400 – 1000 V DC 48 V (or 200 – 500 V high-voltage stacks)
Typical continuous current 10 – 20 A 50 – 200 A
Binding constraint Voltage drop Thermal capacity + heat dissipation
Voltage-drop budget ≤1–2 % of 600 V (6–12 V) ≤1 % of 48 V (0.5 V)
Load profile Daytime, sun-following Continuous charge/discharge, night included
Fault current Limited by module string Very high on lithium banks

Two consequences follow immediately. First, the same ampacity rules that leave PV strings comfortably sized will run hot on a battery trunk. Second, every extra milliohm matters twice — once as heat, once as sag under load, because on a 48 V bus a single volt of drop is already 2 %.

Sizing: the four steps in order

Step 1 — design current with the continuous factor. Inverter ratings are continuous; apply the usual 125 % factor to a continuous load, so a 100 A inverter plans for 125 A of conductor capacity before any correction.

Step 2 — thermal capacity. Use the applicable ampacity table for the insulation class (90 °C XLPE battery cable is the common construction) and then respect the terminal limitation: lugs and breaker terminals are often rated 75 °C, which caps the column you may use regardless of the insulation. Capacity also derates in hot battery rooms and in bundles — the same derating logic described for rooftops in the rooftop cable guide applies to a battery enclosure at 40 – 50 °C.

Step 3 — voltage drop on the real numbers. For a two-wire DC run: ΔU = 2 × I × L × ρ / A, with ρ ≈ 0.023 Ω·mm²/m for warm copper. Worked examples for a 48 V bank, 100 A continuous, one-way length as shown:

One-way run 25 mm² 35 mm² 50 mm² 70 mm²
2 m 0.37 V — 0.77 % 0.26 V — 0.55 % 0.18 V — 0.38 % 0.13 V — 0.27 %
3 m 0.55 V — 1.15 % 0.39 V — 0.82 % 0.28 V — 0.57 % 0.20 V — 0.41 %

At 2 m, 25 mm² squeaks under 1 %; at 3 m it fails. And drop is only half the story — the other half is heat:

Cross-section Conductor heat at 100 A (2 m run)
25 mm² 37 W
35 mm² 26 W
50 mm² 18 W
70 mm² 13 W

37 W dissipated continuously inside a battery cabinet is a self-inflicted thermal problem — it warms the batteries, which ages them, in a loop. One size up halves the heat.

Step 4 — terminals and workmanship. At these currents the joint, not the conductor, is the weak point: compression lugs crimped with the correct die, torqued to spec, and checked after the first weeks of thermal cycling. A terminal that runs warm will eventually carbonise its insulation regardless of how generous the cross-section is.

For high-voltage stacked systems (200 – 500 V), the pressure eases: a 400 V / 25 A stack over 3 m on 10 mm² drops under 0.1 %, and sizing becomes a conventional thermal exercise. The low-voltage, high-current corner is where storage cabling bites.

Protection: the lithium fault-current problem

A lithium bank can deliver far more fault current than the same capacity in lead-acid, and every protective device in the DC path must be able to interrupt that current at DC voltage — which is a much harder duty than AC interruption, because DC does not pass through zero to extinguish the arc.

Practical implications:

  • Class T fuses are the common recommendation on lithium battery mains: a high DC interrupting rating in a compact package. An underspecified breaker or fuse may clear the circuit once and fail, or fail to clear at all.
  • Fuse at the battery positive, as close to the terminal as practical — conductor length between the battery and its protection is unprotected length.
  • Disconnect ratings matter as much as conductor ratings: switches and breakers in the DC path need DC ratings at the system voltage, not AC ratings borrowed from a datasheet.

Cable construction completes the picture: fine-stranded, flexible copper conductors make terminal work feasible at these sizes, and tinned variants earn their premium in humid or coastal battery rooms — the same corrosion logic as in the conductor material comparison.

Regulatory context in one paragraph

Storage wiring sits under its own rules, not the PV array rules: NEC Article 706 governs energy storage systems in the US, systems are certified as complete units under UL 9540, and the battery/inverter combination typically defines the permitted conductor sizes and protective devices in its installation manual. The manual's conductor table is a floor, not a ceiling — field-routed distances are usually longer than the certified configuration assumed, and the sizing arithmetic above is how you cover the difference honestly.

Five mistakes worth avoiding

  1. Reusing PV sizing instincts. 100 A at 48 V is a different regime; check heat, not just drop.
  2. Skipping the 125 % continuous factor. Battery loads are continuous by definition; the margin is not optional.
  3. Ignoring the 75 °C terminal cap. Insulation rated 90 °C does not help if the lug terminates at a 75 °C rating.
  4. Long unprotected runs from the battery terminal. Protection belongs at the source, before the first metre of cable.
  5. AC-rated breakers in DC paths. DC arcing does not self-extinguish; devices must carry explicit DC interrupting ratings.

FAQ

Q1: Can I use PV wire (UL 4703) for battery-to-inverter connections? A: Its electrical construction is suitable — 90 °C, UV-rated single-core copper — but PV wire is built around string currents and UV duty, not 100 A continuous trunk runs. What matters more in practice is conductor size, fine stranding for terminal work, and following the ESS installation manual and NEC 706 requirements for the circuit.

Q2: Why is voltage drop so much harder at 48 V? A: The budget scales with voltage. One percent of a 600 V string is 6 V; one percent of a 48 V bus is 0.48 V — and the current is five to ten times higher, so the conductor must be several sizes larger just to lose the same fraction.

Q3: What size cable does a 100 A battery inverter need? A: Plan for 125 A after the continuous factor, then choose by ampacity table, terminal temperature rating and the drop table above. In metric terms this typically lands at 50 – 70 mm² for short runs; confirm against the applicable table and the inverter manual before purchase.

Q4: Why do lithium systems specify Class T fuses? A: Lithium banks can source very high fault current, and a protective device must interrupt that current at DC voltage. Class T fuses combine a high DC interrupting rating with fast clearance; ordinary AC-rated breakers or automotive fuses may not interrupt a lithium DC fault at all.

Q5: Is welding cable acceptable for battery runs? A: Its flexibility is attractive, but acceptance depends on the listing and the jurisdiction — welding cable is not listed for building wiring in the same way, and AHJs commonly reject it where a listed battery cable construction is required. Fine-stranded, listed battery cable gives the same workability without the compliance question.

Sourcing note

🔴 Disclaimer: conductor tables, protective-device ratings and ESS certification requirements vary by jurisdiction and system model; the figures above are typical worked examples and must be confirmed against the applicable code edition, the UL 9540 system certification and the battery/inverter installation manual before design sign-off. This article is engineering guidance, not a design certification.